Add to Cart
Transformer Insulation Oil Dielectric Strength Test Kit Portable Insulating Oil Breakdown Voltage Bdv Tester
Insulatingoil dielectric strength tester complies with astm d1816 astm d877 standard. It is testing all kinds of Insulation Oil’s Dielectric Strength Value.Our company has three different types of single-cup oil bdv tester, three-cup oil bdv tester and six-cup oil bdv tester.
2. The instrument is equipped with temperature and humidity and clock display function, and can be customized for infrared oil temperature measurement.
3. the instrument is equipped with a wide range of built-in watchdog circuit to eliminate the phenomenon of deadlock;
4. a variety of standard options, the instrument program with GB/T507-1986, GB/T507-2002, DL429.9, IEC156 and self-programming operation, can adapt to different users of a variety of options; 5;
5. the instrument oil cup is made of special glass and polymer materials, finely processed to eliminate the occurrence of oil leakage and corrosion;
6. the unique high voltage end sampling design of the instrument allows the test value to enter directly into the A/D converter, avoiding the error caused in the analog circuit and making the measurement results more accurate;
7. the instrument has internal functions such as over-current, over-voltage, short-circuit protection, etc., and has an extremely strong anti-interference capability and good electromagnetic compatibility;
8. can switch between English and Chinese at will to meet any customer needs;
9. the instrument itself has a data analysis function to assist staff in determining the quality of oil products;
10. USB data transmission (optional);
Booster capacity | 1.5kVA |
Boost speed | 0.5kV/s-5.0kV/s (in 0.5 increments) ten steps of your choice Error 0.2kV/s |
Output voltage | 0 ~ 80 kV (optional) |
Voltage accuracy | (2% of reading + 2 words) |
Power distortion rate | <1% |
Electrode gap standard | 2.5 mm |
Test cups | 1 cups |
Resting time | 900S (0-9000 S optional) |
Interval resting time | 300S (0-900 S optional) |
Stirring time | 15S (0-250S optional) |
External dimensions | 430*350*370mm |
Instrument weight | 36kg |
Ambient temperature | 0~40℃ |
Relative humidity | ≤85% |
Operating power supply | AC 220V (1 ± 10%) |
Power consumption | <200 W |